This paper analyses the frequency stability of ac grids in the presence of non-dispatchable generation and stochastic loads. Its main goal is to evaluate conditions in which the system is robust to large, persistent active power disturbances without recurring to time-domain simulations. Considering the ongoing energy transition to more renewable sources, defining robustness boundaries is a key topic for power system planning and operation. However, much of the research on long-term studies has not dealt with robust dynamic constraints, while short-term analyses usually depend on time-consuming simulations to evaluate nonlinearities. To bridge this gap, the authors derive an algebraic equation that provides sufficient conditions for robust frequency stability in ac power systems and a relationship among four key quantities: the maximum active power perturbation, the minimum system damping, the steady-state and the transient frequency limits. To achieve this goal, it uses a nonlinear average model of the ac grid and Lyapunovs direct method extended by perturbation analysis requiring only limited knowledge of the system parameters. The algebraic calculations are validated using time-domain simulations of the IEEE 39-bus test system and results are compared to the traditional Swing Equation model.

Sufficient Conditions for Robust Frequency Stability of AC Power Systems / Alves, E. F.; Bergna, G.; Brandao, D. I.; Tedeschi, E.. - In: IEEE TRANSACTIONS ON POWER SYSTEMS. - ISSN 0885-8950. - 2021, 36:3(2021), pp. 2684-2692. [10.1109/TPWRS.2020.3039832]

Sufficient Conditions for Robust Frequency Stability of AC Power Systems

Tedeschi E.
2021-01-01

Abstract

This paper analyses the frequency stability of ac grids in the presence of non-dispatchable generation and stochastic loads. Its main goal is to evaluate conditions in which the system is robust to large, persistent active power disturbances without recurring to time-domain simulations. Considering the ongoing energy transition to more renewable sources, defining robustness boundaries is a key topic for power system planning and operation. However, much of the research on long-term studies has not dealt with robust dynamic constraints, while short-term analyses usually depend on time-consuming simulations to evaluate nonlinearities. To bridge this gap, the authors derive an algebraic equation that provides sufficient conditions for robust frequency stability in ac power systems and a relationship among four key quantities: the maximum active power perturbation, the minimum system damping, the steady-state and the transient frequency limits. To achieve this goal, it uses a nonlinear average model of the ac grid and Lyapunovs direct method extended by perturbation analysis requiring only limited knowledge of the system parameters. The algebraic calculations are validated using time-domain simulations of the IEEE 39-bus test system and results are compared to the traditional Swing Equation model.
2021
3
Alves, E. F.; Bergna, G.; Brandao, D. I.; Tedeschi, E.
Sufficient Conditions for Robust Frequency Stability of AC Power Systems / Alves, E. F.; Bergna, G.; Brandao, D. I.; Tedeschi, E.. - In: IEEE TRANSACTIONS ON POWER SYSTEMS. - ISSN 0885-8950. - 2021, 36:3(2021), pp. 2684-2692. [10.1109/TPWRS.2020.3039832]
File in questo prodotto:
File Dimensione Formato  
Sufficient_Conditions_for_Robust_Frequency_Stability_of_AC_Power_Systems.pdf

accesso aperto

Tipologia: Versione editoriale (Publisher’s layout)
Licenza: Creative commons
Dimensione 806.12 kB
Formato Adobe PDF
806.12 kB Adobe PDF Visualizza/Apri