The paper presents the development of an innovative cost-effective fire protection system for steel columns, which is quick and easy to install and to dismantle. In terms of assembly, this protection is designed to be a plug-and-play system, which is made of two U-shaped half-protections that encapsulate a column. They are composed of high-density rock wool boards arranged in U-shape steel sheets presenting a system of claws to ensure their connection. Small-scale experimental tests were performed to evaluate the insulating efficiency of the system and the thermal behaviour of the connection claws. Numerical models were then developed with the finite elements software ABAQUS and SAFIR and were successively calibrated based on experimental results. Subsequently, full-scale experimental tests were performed according to the European standard of regulation EN13381-4 and the results certified that the fire protection is effective for steel profiles with section factor ranging from 42 to 103 m−1 to maintain the steel temperature below 550 °C when exposed to a standard fire for 120 min. Finally, a cost analysis was performed to attest the competitivity of the plug-and-play fire protection system by considering direct and indirect costs.

Development of a Plug-and-Play Fire Protection System for Steel Columns / Randaxhe, Jérôme; Popa, Nicoleta; Vassart, Olivier; Tondini, Nicola. - In: FIRE SAFETY JOURNAL. - ISSN 0379-7112. - 121 (2021):(2021), pp. 103272/1-103272/26. [10.1016/j.firesaf.2020.103272]

Development of a Plug-and-Play Fire Protection System for Steel Columns

Randaxhe, Jérôme;Tondini, Nicola
2021-01-01

Abstract

The paper presents the development of an innovative cost-effective fire protection system for steel columns, which is quick and easy to install and to dismantle. In terms of assembly, this protection is designed to be a plug-and-play system, which is made of two U-shaped half-protections that encapsulate a column. They are composed of high-density rock wool boards arranged in U-shape steel sheets presenting a system of claws to ensure their connection. Small-scale experimental tests were performed to evaluate the insulating efficiency of the system and the thermal behaviour of the connection claws. Numerical models were then developed with the finite elements software ABAQUS and SAFIR and were successively calibrated based on experimental results. Subsequently, full-scale experimental tests were performed according to the European standard of regulation EN13381-4 and the results certified that the fire protection is effective for steel profiles with section factor ranging from 42 to 103 m−1 to maintain the steel temperature below 550 °C when exposed to a standard fire for 120 min. Finally, a cost analysis was performed to attest the competitivity of the plug-and-play fire protection system by considering direct and indirect costs.
2021
Randaxhe, Jérôme; Popa, Nicoleta; Vassart, Olivier; Tondini, Nicola
Development of a Plug-and-Play Fire Protection System for Steel Columns / Randaxhe, Jérôme; Popa, Nicoleta; Vassart, Olivier; Tondini, Nicola. - In: FIRE SAFETY JOURNAL. - ISSN 0379-7112. - 121 (2021):(2021), pp. 103272/1-103272/26. [10.1016/j.firesaf.2020.103272]
File in questo prodotto:
File Dimensione Formato  
FIRE_PROTECTION_FSJ_OPEN_ACCESS.pdf

accesso aperto

Tipologia: Pre-print non referato (Non-refereed preprint)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 4.34 MB
Formato Adobe PDF
4.34 MB Adobe PDF Visualizza/Apri
1-s2.0-S0379711220307906-main_compressed.pdf

accesso aperto

Tipologia: Versione editoriale (Publisher’s layout)
Licenza: Tutti i diritti riservati (All rights reserved)
Dimensione 2.86 MB
Formato Adobe PDF
2.86 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11572/288323
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 6
  • ???jsp.display-item.citation.isi??? 5
social impact